Expert Features

  • 3KVA / 2700W Output: Provides rated output capacity of 3KVA/2.7KW, with an output power factor of 0.9.
  • Online Pure Sine Wave: Delivers sine-wave output with THD below 3% for linear loads and below 8% for nonlinear loads.
  • Zero Transfer Time: Transfers between AC and battery in 0ms to support continuous load operation.
  • Active Input PFC: Input power factor is above 0.98.
  • Generator Compatible: Can be connected to a generator.
  • Wide Input Range: Accepts 115–300VAC ±5% input voltage and (45–55)Hz ±0.5Hz input frequency, designed for challenging grid environments.
  • Internal 72V Battery Group: Uses an internal battery group; the supplied listing identifies six 12V 7Ah batteries.
  • Backup Runtime: Standard backup time is at least 10 minutes at half load and at least 5 minutes at full load.
  • LCD Control Panel: The product image shows a front LCD and control buttons for viewing UPS status.

 Expert Specs

SpecificationDetails
BrandNCTS
ModelNU3K6S / NCTS-NU3K6S
Product typeOnline UPS
Output waveformPure sine wave
Rated output capacity3KVA / 2.7KW
Rated voltage220VAC
Input voltage range115–300VAC ±5%
Input frequency range(45–55)Hz ±0.5Hz
Bypass voltage80VAC × (1±5%) to 285VAC × (1±5%)
Battery group voltage72V
Battery methodInternal
Battery configuration in supplied product title6 × 12V 7Ah
Standard backup timeHalf load: ≥10 minutes; full load: ≥5 minutes
Maximum input current at power-on<150% of rated current
Standard charging time5 hours to 90%; depends on external battery group capacity for long-running operation
Output voltage220VAC ±1% in inverter output
Output frequency50±5Hz with normal AC input; 50Hz ±1% when AC input is abnormal
Waveform distortionTHD <3% at linear load; THD <8% at nonlinear load
Output power factor0.9
Input power factor correctionActive PFC; input power factor >0.98
Overload ability130% load for at least 30 seconds; recovery point is 90% load
Output current peak coefficient3:1
AC-to-battery transfer time0ms
Communication and monitoringRS232 (can transfer to 485), dry mode, smart slot expandable to SNMP, SMS, and other monitoring methods
Generator connectionSupported
Net weight22.89kg
Gross weight25.38kg
Unit dimensions (W × H × D)460 × 192 × 333mm
Carton dimensions (W × H × D)612 × 327 × 485mm